Plan Review Notes
Plan Review Notes For Permit 21030785
Permit Number 21030785
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-29 15:45:4703/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.1.1, PLEASE GIVE ALL DIMENSIONS FOR
 FIXTURE CLEARANCES PER THE FLORIDA BUILDING CODE AND
 FLORIDA ACCESSIBILITY CODE.
  
 2. ON SHEET A9.0.1, 7;
  
 A. PLEASE SHOW THE WATER CLOSET FLUSH CONTROL LOCATION
 PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS.
  
 B. PLEASE THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE
 40? TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC.
 603.3.
  
 C. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 D. PLEASE SHOW THE REAR AND SIDE DIMENSIONS FOR GRAB
 BARS PER THE 2020 FBC ACC SEC. 604.5.
  
 E. PLEASE PROVIDE THE KNEE AND TOE CLEARANCES FOR THE
 LAVATORY PER THE 2020 FBC ACC SEC. 306.3 TOE CLEARANCE.
  
 F. ON DETAIL B, IT SHOWS 1?- 6? MAXIMUM, AND PLEASE ADD
 THE TO THE CENTERLINE OF THE WATER CLOSET SHALL BE
 1?-4? INCHES MINIMUM FROM THE SIDEWALL PER THE 2020 FBC
 ACC. 604.2.
  
 G. THE TOILET SEATS NEED TO BE 17? INCHES TO 19? INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020
 FBC ACC SEC. 604.4 SEATS.
  
 3. THE WASHER IS CONSIDERED FOR COMMERCIAL USE AND WILL
 REQUIRE A LINT INTERCEPTOR. PLEASE SHOW AND PROVIDE
 SPECIFICATION SUPPLY DETAILS OR NOTES PER THE 2020 FBC
 SEC. 1003.6.
  
 4. ON SHEET P0.1;
 A. THE ICE MAKER AND COFFEE MAKER SHALL BE EQUIPPED
 WITH AN INLINE VACUUM BREAKER THAT COMPLIES WITH ASSE
 1024 PER THE 2020 FBC ACC SEC. 608.13.10.
  
 B. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1.
  
 5. ON SHEET P3.1, WASHING MACHINE VALVES MUST BE
 ACCESSIBLE FOR SHUTTING OFF WITHOUT MOVING UNITS, 2020
 FBC P 604.10.3 ACCESS. ACCESSIBLE SIGNIFIES ACCESS THAT
 REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR
 REMOVABLE OBSTRUCTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved