Date |
Text |
2021-03-29 15:45:47 | 03/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A1.1.1, PLEASE GIVE ALL DIMENSIONS FOR |
| FIXTURE CLEARANCES PER THE FLORIDA BUILDING CODE AND |
| FLORIDA ACCESSIBILITY CODE. |
| |
| 2. ON SHEET A9.0.1, 7; |
| |
| A. PLEASE SHOW THE WATER CLOSET FLUSH CONTROL LOCATION |
| PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS. |
| |
| B. PLEASE THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE |
| 40? TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. |
| 603.3. |
| |
| C. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| |
| D. PLEASE SHOW THE REAR AND SIDE DIMENSIONS FOR GRAB |
| BARS PER THE 2020 FBC ACC SEC. 604.5. |
| |
| E. PLEASE PROVIDE THE KNEE AND TOE CLEARANCES FOR THE |
| LAVATORY PER THE 2020 FBC ACC SEC. 306.3 TOE CLEARANCE. |
| |
| F. ON DETAIL B, IT SHOWS 1?- 6? MAXIMUM, AND PLEASE ADD |
| THE TO THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| 1?-4? INCHES MINIMUM FROM THE SIDEWALL PER THE 2020 FBC |
| ACC. 604.2. |
| |
| G. THE TOILET SEATS NEED TO BE 17? INCHES TO 19? INCHES |
| MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020 |
| FBC ACC SEC. 604.4 SEATS. |
| |
| 3. THE WASHER IS CONSIDERED FOR COMMERCIAL USE AND WILL |
| REQUIRE A LINT INTERCEPTOR. PLEASE SHOW AND PROVIDE |
| SPECIFICATION SUPPLY DETAILS OR NOTES PER THE 2020 FBC |
| SEC. 1003.6. |
| |
| 4. ON SHEET P0.1; |
| A. THE ICE MAKER AND COFFEE MAKER SHALL BE EQUIPPED |
| WITH AN INLINE VACUUM BREAKER THAT COMPLIES WITH ASSE |
| 1024 PER THE 2020 FBC ACC SEC. 608.13.10. |
| |
| B. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE |
| REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1. |
| |
| 5. ON SHEET P3.1, WASHING MACHINE VALVES MUST BE |
| ACCESSIBLE FOR SHUTTING OFF WITHOUT MOVING UNITS, 2020 |
| FBC P 604.10.3 ACCESS. ACCESSIBLE SIGNIFIES ACCESS THAT |
| REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR |
| REMOVABLE OBSTRUCTION. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |