2021-03-29 16:03:31 | 03/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A1.1.1, |
| A. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER |
| THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| B. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING |
| DETAILS OF THE GAS VENT(S) PER THE 2020 FBC FG SECS. |
| 502 THRU 505. |
| |
| C. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC FG SEC.305. |
| |
| D. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR |
| THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC |
| RES. SEC. G2421.1. |
| |
| F. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017 |
| FBC FG SEC 410.2. |
| |
| G. THE DRIP LEG ON EQUIPMENT IS SHOWN INSTALLED |
| INCORRECTLY. PLEASE REFER TO FIGURE 408.4 METHOD OF |
| INSTALLING A TEE FITTING SEDIMENT TRAP. |
| |
| H. SUBMIT COMBUSTION AIR CALCULATIONS FOR A GAS HEATER. |
| THE BUILDING?S MECHANICAL VENTILATION SYSTEM PROVIDES |
| COMBUSTION AIR. THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| COMBUSTION AIR RATE AND THE REQUIRED VENTILATION AIR |
| PER THE 2020 FBC FG SEC. 304.9.3. COMBINED COMBUSTION |
| AIR AND VENTILATION AIR SYSTEM. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP EXPEDITE |
| YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |