2021-03-29 16:03:3103/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.1.1,
 A. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER THE 2020 FBC FG SECS.
 502 THRU 505.
  
 C. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FG SEC.305.
  
 D. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 F. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 G. THE DRIP LEG ON EQUIPMENT IS SHOWN INSTALLED
 INCORRECTLY. PLEASE REFER TO FIGURE 408.4 METHOD OF
 INSTALLING A TEE FITTING SEDIMENT TRAP.
  
 H. SUBMIT COMBUSTION AIR CALCULATIONS FOR A GAS HEATER.
 THE BUILDING?S MECHANICAL VENTILATION SYSTEM PROVIDES
 COMBUSTION AIR. THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE AND THE REQUIRED VENTILATION AIR
 PER THE 2020 FBC FG SEC. 304.9.3. COMBINED COMBUSTION
 AIR AND VENTILATION AIR SYSTEM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP EXPEDITE
 YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  