Plan Review Notes
Plan Review Notes For Permit 21030743
Permit Number 21030743
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-15 11:32:22JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00
 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1 SUBMITTED MIAMI-DADE COUNTY NOA 19-0311.04 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(8). ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 ENGINEERED SIGNED AND SEALED CALCULATIONS MAY BE
 REQUIRED.
 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 14-0603.01 HAS EXPIRED AND IS NO LONGER VALID. PLEASE
 PROVIDE TWO SETS OF PRODUCT APPROVALS/NOA?S FOR THE
 RIDGE CAP SHINGLES TO BE USED.
 3. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA
 18-1217.13 COVERS MULTIPLE INSTALLATION METHODS; CURB
 MOUNT & DSF SELF-FLASHING. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
  