2021-04-08 23:48:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN SHOWS "ROYAL PALM BEACH" INSTEAD OF WEST PALM |
| BEACH, FOR ADDRESS. PLEASE PROVIDE CORRECTION. FBC |
| 107.2.1 |
| |
| 2. PLAN REFERENCES 2014 NATIONAL ELECTRICAL CODE AS |
| STANDARD. CURRENT ADOPTED ELECTRICAL CODE PER FLORIDA |
| STATUTES IS THE 2017 NEC. PLEASE PROVIDE CORRECTION. |
| FBC 107.2.1 |
| |
| 3. PROVIDE NOTE ON PLAN THAT STATES ANY DC THROUGH |
| BUILDING WILL BE IN METAL CONDUIT PER NEC 690.31G |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |