Plan Review Notes For Permit 21030664 |
Permit Number |
21030664 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-07 09:16:00 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PERMIT APPLICATION SPECIFIES A 22 KW GENERATOR | | AND THE OTHER PERMIT DOCUMENTS SPECIFY A 32 KW | | GENERATOR. CLARIFY. FBC AMENDMENTS 107.2.1 | | | | 2) SUBMIT PRODUCT APPROVALS OR SIGNED AND SEALED SITE | | SPECIFIC ENGINEERING FOR THE PRE-FABRICATED GENERATOR | | PAD. FBC AMENDMENTS 107.3.4 | | |
|