Plan Review Notes
Plan Review Notes For Permit 21030661
Permit Number 21030661
Review Stop E
Sequence Number 1
Notes
Date Text
2021-05-07 14:19:05CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW
  
 1) SERVICE CONDUCTORS TO EACH OF THE 200 AMPS ATS ARE
 2/0 CU FOR EACH OF THE . NEC 310.15(B)(7) DOES NOT
 ALLOW DERATING OF SERVICE
 CONDUCTORS WHEN SERVIDE CONDUCTORS ARE NOT SUPPLYING
 THE ENTIRE LOAD. MINIMUM SIZE SHALL BE #3/0 CONDUCTORS
 OR PROVIDE CLARIFICATION.
  
  
 SINCERELY,
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  