Plan Review Notes For Permit 21030651 |
Permit Number |
21030651 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-06-21 09:07:09 | 1) SHOW THE DISTANCE OF THE LP TANK FROM THE DRIVEWAY. | | IF THE TANK IS WITHIN 10 FT. OF THE DRIVEWAY, THE TANK | | SHALL BE BURIED A MNIMUM OF 18 INCHES BELOW GRADE PER | | NFPA 58 SEC. 6.8.6.1 (B). | | 2) IF THE LP TANK IS WITHIN 10 FT. OF THE DRIVEWAY, | | VEHICULAR BARRIER PROTECTION SHALL BE PROVIDED FOR THE | | CONTAINER'S FITTING HOUSING, HOUSING COVER, CONTAINER | | CONNECTIONS, AND PIPING.NFPA 58, SEC.6.8.6.1(C). | | 3) THE PERMIT IS FOR LP GAS BUT THE SUBMITTED GAS | | SIZING TABLES ARE FOR NATURAL GAS. SUBMIT THE CORRECT | | SIZING TABLES. | | 4) WHERE CONNECTED TO RIGID PIPING, A UNION IS REQUIRED | | ON THE GAS PIPING WITHIN 1 FT. UPSTREAM OR DOWNSTREAM | | OF THE REGULATORS.FBC-FUEL GAS SEC.410.2 (7). | | 5) INDICATE ON THE PLAN THE TYPE OF AUGER ANCHOR TO BE | | USED BASED ON THE CLASS OF SOIL FROM THE TABLE FROM TIE | | DOWN ENGINEERING. WPB AMEND. TO FBC SEC. 107.2.1. | | 6) THE GAS PLAN STATES THE GAS CODES ARE BASED ON 402.4 | | SERIES OF FBC CODES. THERE ARE NO 402.4 SERIES OF FBC | | CODES. CLARIFY. | | 7) THE SUBMITTED SPEC SHEETS FOR THE MODEL 496 ARE | | ILLEGIBLE. SUBMIT NEW SHEETS. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 8) THE SUBMITTED SPECICIFICATION (PAGES 8,10) FOR THE | | EXCELA-FLO MEGR-1100 & 1200 SERIES REGULATOR IS | | ILLEGIBLE. SUBMIT A CLEAR SHEET FOR REVIEW. WPB AMEND. | | TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|