Plan Review Notes
Plan Review Notes For Permit 21030651
Permit Number 21030651
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-21 09:07:091) SHOW THE DISTANCE OF THE LP TANK FROM THE DRIVEWAY.
 IF THE TANK IS WITHIN 10 FT. OF THE DRIVEWAY, THE TANK
 SHALL BE BURIED A MNIMUM OF 18 INCHES BELOW GRADE PER
 NFPA 58 SEC. 6.8.6.1 (B).
 2) IF THE LP TANK IS WITHIN 10 FT. OF THE DRIVEWAY,
 VEHICULAR BARRIER PROTECTION SHALL BE PROVIDED FOR THE
 CONTAINER'S FITTING HOUSING, HOUSING COVER, CONTAINER
 CONNECTIONS, AND PIPING.NFPA 58, SEC.6.8.6.1(C).
 3) THE PERMIT IS FOR LP GAS BUT THE SUBMITTED GAS
 SIZING TABLES ARE FOR NATURAL GAS. SUBMIT THE CORRECT
 SIZING TABLES.
 4) WHERE CONNECTED TO RIGID PIPING, A UNION IS REQUIRED
 ON THE GAS PIPING WITHIN 1 FT. UPSTREAM OR DOWNSTREAM
 OF THE REGULATORS.FBC-FUEL GAS SEC.410.2 (7).
 5) INDICATE ON THE PLAN THE TYPE OF AUGER ANCHOR TO BE
 USED BASED ON THE CLASS OF SOIL FROM THE TABLE FROM TIE
 DOWN ENGINEERING. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE GAS PLAN STATES THE GAS CODES ARE BASED ON 402.4
 SERIES OF FBC CODES. THERE ARE NO 402.4 SERIES OF FBC
 CODES. CLARIFY.
 7) THE SUBMITTED SPEC SHEETS FOR THE MODEL 496 ARE
 ILLEGIBLE. SUBMIT NEW SHEETS. WPB AMEND. TO FBC SEC.
 107.2.1.
 8) THE SUBMITTED SPECICIFICATION (PAGES 8,10) FOR THE
 EXCELA-FLO MEGR-1100 & 1200 SERIES REGULATOR IS
 ILLEGIBLE. SUBMIT A CLEAR SHEET FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  