Plan Review Notes
Plan Review Notes For Permit 21030608
Permit Number 21030608
Review Stop G
Sequence Number 3
Notes
Date Text
2021-05-06 16:56:573RD REVIEW FBC-2020 RES.
 PERMIT- 21030608
 5/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 NFPA- 58
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CLARIFY WHICH LP GAS REGULATORS WILL BE
 INSTALLED AT THE TANK AND AT THE SERVICE ENTRANCE TO
 THE HOUSE. THE MAKE AND MODEL SELECTIONS SHOWN ON THE
 RISER DRAWINGS BY ROBERT PETTET AND JERIMIAH CAY DO NOT
 MATCH- SECTION 107.2.1 WPB.
  
 2) JERIMIAH CAY RISER:
 A) THE 1/2 IN. SCHEDULE 40 GAS PIPING SUPPLYING THE
 COOKTOP AND FIREPLACE IS UNDERSIZED-. A MIN 3/4 IN.
 PIPE IS REQUIRED BASED ON THE SIZING TABLE YOU HAVE
 SELECTED- TABLE 402.4(28) FBC FG.
 B) 2ND REQUEST: PLEASE PROVIDE THE EHD OF THE 3/4 IN.
 CSST BASED ON THE SIZING TABLE YOU HAVE SELECTED- TABLE
 402.4(32) FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  