2021-05-06 16:56:57 | 3RD REVIEW FBC-2020 RES. |
| PERMIT- 21030608 |
| 5/6/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| NFPA- 58 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE CLARIFY WHICH LP GAS REGULATORS WILL BE |
| INSTALLED AT THE TANK AND AT THE SERVICE ENTRANCE TO |
| THE HOUSE. THE MAKE AND MODEL SELECTIONS SHOWN ON THE |
| RISER DRAWINGS BY ROBERT PETTET AND JERIMIAH CAY DO NOT |
| MATCH- SECTION 107.2.1 WPB. |
| |
| 2) JERIMIAH CAY RISER: |
| A) THE 1/2 IN. SCHEDULE 40 GAS PIPING SUPPLYING THE |
| COOKTOP AND FIREPLACE IS UNDERSIZED-. A MIN 3/4 IN. |
| PIPE IS REQUIRED BASED ON THE SIZING TABLE YOU HAVE |
| SELECTED- TABLE 402.4(28) FBC FG. |
| B) 2ND REQUEST: PLEASE PROVIDE THE EHD OF THE 3/4 IN. |
| CSST BASED ON THE SIZING TABLE YOU HAVE SELECTED- TABLE |
| 402.4(32) FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |