Plan Review Notes
Plan Review Notes For Permit 21030531
Permit Number 21030531
Review Stop HIST
Sequence Number 2
Notes
Date Text
2021-04-08 12:10:27PREVIOUS COMMENTS NOT ADDRESSED.
  
 THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. PROVIDE A GRAPHIC OF THE EXISTING DOOR AND PROPOSED
 DOOR.
 2. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOW
 MATERIAL AND THE PROPOSED WINDOWS EXTERIOR FRAME COLOR,
 GLASS GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION
 WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW
 MARKED.
 3. INCLUDE THE ORDER QUOTE DETAIL.
  
 IF THE STREET FACING WINDOWS ARE WOOD. THESE WINDOWS
 MAY NEED TO BE RETAINED AND RESTORED. ADDITIONAL
 INFORMATION MAY BE REQUIRED. PLEASE CONTACT STAFF IF
 YOU HAVE ANY QUESTIONS.
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  