Plan Review Notes For Permit 21030530 |
Permit Number |
21030530 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-22 09:10:54 | 1ST REVIEW FBC-2020 RES. FUEL GAS | | PERMIT- 21030530 | | 3/22/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS RISER: PLEASE SHOW THE INTERIOR GAS PIPING RUN | | TO THE EXISTING RANGE AND WATER HEATER INSTALLED UNDER | | PERMIT 02070042. SHOW THE INDIVIDUAL BTU LOADS, THE | | TOTAL BTUS OF THE SYSTEM, AND THE TOTAL DEVELOPED | | LENGTH FROM THE METER TO THE MOST REMOTE OUTLET- | | SECTIONS G2413.3 & G2413.4 FBC RES. | | | | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING | | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 | | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|