2021-06-04 10:14:28 | 06/04/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| 3. THE ISOMETRIC DRAWING CLEARLY SHOWS THE LENGTH OF |
| ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. SECS. |
| G2413.4.1, G2413.4.2. |
| |
| 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED FOR |
| EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| G2413. FOR FUTURE GENERATOR, PLEASE PROVIDE AN |
| ESTIMATED SIZE AND SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| THE 2020 FBC RES. SEC. G2413.4.1. |
| |
| 7. PLEASE INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) |
| ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| |
| 8. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| |
| 9. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE INSPECTION TIME PER THE 2020 FBC |
| RES. SEC. G2413.2 AND G2404.3. |
| |
| 10. PLEASE PROVIDE THE SIZING TABLE USED IN THE DESIGN |
| FOR THE GAS SYSTEM OR PLACE A NOTE ON SETS OF PLANS |
| LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER |
| STANDARD USED IN THE DESIGN OF THIS SYSTEM PER THE 2020 |
| FBC RES. SEC. G2413.3. |
| |
| 11. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3. |
| BUILDING PERMITS VALUATIONS. |
| |
| 12. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| GD, ACCESS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |