Plan Review Notes For Permit 21030465 |
Permit Number |
21030465 |
|
Review Stop |
Z |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2021-06-18 15:25:20 | THERE ARE STILL AREAS WHERE THE PHOTOMETRIC LEVELS ARE | | EXCEEDING 1.0 FOOTCANDLES. THE AREAS THAT THE ZONING | | CODE SPECIFICALLY DOES NOT ALLOW THIS TO HAPPEN IS AT | | THE BOUNDARY OF THE CPD, WHICH IS ALONG THE AUSTRALIAN | | AVENUE PROPERTY LINE. IN ONE AREA YOU CITE NFPA, BUT | | PLEASE PROVIDE THE SPECIFIC CODE PROVISION YOU?RE USING | | AS JUSTIFICATION FOR YOUR DESIGN. ADDITIONALLY, YOUR | | PLANS SPEAK OF A SCREEN WALL ON THE ADJACENT PROPERTY?I | | AM NOT FAMILIAR WITH THIS WALL?AND IF IT DOESN?T EXIST | | TODAY, I HAVEN?T SEEN ANY PERMITS (AND MORE IMPORTANTLY | | PERMISSION FROM THE ADJACENT PROPERTY OWNER) FOR THE | | CONSTRUCTION OF SUCH WALL. THE CODES ARE IN PLACE TO | | MINIMIZE THE IMPACT OF YOUR LIGHTING ON ADJACENT | | PROPERTIES (I.E. SPILLOVER) AS THEY SHOULD NOT BE | | INCONVENIENCED OR IMPACTED BY WHAT IS HAPPENING ON YOUR | | PROPERTY. THERE ARE A LOT OF AREAS WHERE THIS SPILLOVER | | IS HAPPENING. |
|