2021-04-22 10:56:53 | CODES IN EFFECT |
| |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| 7TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| |
| 1) SERVICE CONDUCTORS ARE UNDERSIZED AS PER THE LOAD |
| CALCULATIONS SUBMITTED. PLEASE PROVIDE ADEQUATE |
| CONDUCTORS. NEC 230.23. PLEASE NOTICE THAT THE AMPACITY |
| OF THE SERVICE CONDUCTORS CANNOT BE DERATED IN THIS |
| CASE. NEC 310.15(7). |
| DEMAND LOAD INDICATED IS 131 AMPS (BUILD 1) + 96 AMPS |
| (BUILD 2) = 227 AMPS. MINIMUM SIZE FOR SERVICE |
| CONDUCTORS IS 4/0 CU (SERVICE CONDUCTORS CANNOT BE |
| DERATED NEC 310.15(7)) |
| |
| CORRECTED |
| |
| 2) PLEASE SHOW LOCATION OF SERVICE METERS, DISCONNECTS, |
| AND NEW PANELS. |
| |
| NOT CORRECTED. PLEASE PROVIDE LOCATIONS OF METERS, |
| DISCONNECTS AND PANELS |
| |
| 2) PLEASE SPECIFY SIZE OF BREAKER FOR MAIN DISCONNECT A |
| (150 AMPS). IF NOT USING A BREAKER PLEASE SPECIFY HOW |
| FEEDER FROM DISCONNECT A TO NEW PANEL BUILD IS |
| PROTECTED (TAP RULES?) |
| |
| NOT CORRECTED. WE CANNOT DETERMINE HOW THE FEEDER FROM |
| DISCONNECT A TO PANEL BUILD 1 IS PROTECTED. WHAT IS THE |
| DISTANCE FROM DISCONNECT A TO THE PANEL? DOES THE |
| DISCONNECT HAS AN INTEGRATED BREAKER? |
| |
| 3) PLEASE INDICATE SHORT CIRCUIT INTERRUPTING CAPACITY |
| FOR DISCONNECTS AND PANEL BOARDS. FBC 107 |
| |
| NOT CORRECTED |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| THE RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| MS |
| |
| ENRIQUE QUINONEZ P.E. |
| ELECTRICAL PLANS EXAMINER |
| DEVELOPMENT SERVICES |
| CITY OF WEST PAM BEACH |
| 401 CLEMATIS STREET, 1ST FLOOR |
| WEST PALM BEACH, FL 33401 |
| |
| FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, |
| 561-805-6746. |
| |