2021-04-22 10:56:53CODES IN EFFECT
  
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SERVICE CONDUCTORS ARE UNDERSIZED AS PER THE LOAD
 CALCULATIONS SUBMITTED. PLEASE PROVIDE ADEQUATE
 CONDUCTORS. NEC 230.23. PLEASE NOTICE THAT THE AMPACITY
 OF THE SERVICE CONDUCTORS CANNOT BE DERATED IN THIS
 CASE. NEC 310.15(7).
 DEMAND LOAD INDICATED IS 131 AMPS (BUILD 1) + 96 AMPS
 (BUILD 2) = 227 AMPS. MINIMUM SIZE FOR SERVICE
 CONDUCTORS IS 4/0 CU (SERVICE CONDUCTORS CANNOT BE
 DERATED NEC 310.15(7))
  
 CORRECTED
  
 2) PLEASE SHOW LOCATION OF SERVICE METERS, DISCONNECTS,
 AND NEW PANELS.
  
 NOT CORRECTED. PLEASE PROVIDE LOCATIONS OF METERS,
 DISCONNECTS AND PANELS
  
 2) PLEASE SPECIFY SIZE OF BREAKER FOR MAIN DISCONNECT A
 (150 AMPS). IF NOT USING A BREAKER PLEASE SPECIFY HOW
 FEEDER FROM DISCONNECT A TO NEW PANEL BUILD IS
 PROTECTED (TAP RULES?)
  
 NOT CORRECTED. WE CANNOT DETERMINE HOW THE FEEDER FROM
 DISCONNECT A TO PANEL BUILD 1 IS PROTECTED. WHAT IS THE
 DISTANCE FROM DISCONNECT A TO THE PANEL? DOES THE
 DISCONNECT HAS AN INTEGRATED BREAKER?
  
 3) PLEASE INDICATE SHORT CIRCUIT INTERRUPTING CAPACITY
 FOR DISCONNECTS AND PANEL BOARDS. FBC 107
  
 NOT CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 THE RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved