Plan Review Notes For Permit 21030378 |
Permit Number |
21030378 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-17 15:43:14 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO | | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT | | SHOWS THE REQUIRED WIND DESIGN PRESSURE - PLEASE CIRCLE | | THE ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - | | IF NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS | | FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND | | 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE | | CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT | | APPROVAL. | | 2) I DO NOT SEE A BUILDING PERMIT APPLICATION IN THE | | FOLDER - PLEASE PROVIDE A COMPLETED BUILDING PERMIT | | APPLICATION. | | |
|