Plan Review Notes
Plan Review Notes For Permit 21030362
Permit Number 21030362
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-11 15:00:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REVISE NOTE ON SURVEY. THE GENERATOR EXHAUST IS
 REQUIRED TO BE 10 FEET FROM OPENINGS INTO A BUILDING.
 FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) SUBMIT GENERATOR SPECIFICATIONS AND CUT SHEETS. FBC
 AMENDMENTS 107.2.1
  
 3) SUBMIT GENERATOR PAD AND ANCHORING DETAILS, FBC
 AMENDMENTS 107.2.1
  
  
  
  
  