2021-03-10 13:49:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) IT APPEARS THAT THESE WALLS HAVE ALREADY BEEN |
| INSTALLED AND ARE EXISTING. THIS BUILDING ALSO HAS FIRE |
| SPRINKLER PROTECTION. |
| |
| THE NEW WALLS REQUIRE A REVIEW OF THE EXISTING FIRE |
| SPRINKLER HEAD LOCATION FOR CODE COMPLIANT PROTECTION |
| BY A FIRE SPRINKLER CONTRACTOR. |
| |
| ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE |
| UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE A LETTER OF REVIEW AND |
| COMPLIANCE FROM A FIRE SPRINKLER CONTRACTOR OR PROVIDE |
| A NOTE OF ACKNOWLEDGEMENT THAT A SEPARATE PERMIT WILL |
| BE SUBMITTED WITH SHOP DRAWINGS FOR THE FIRE SPRINKLER |
| MODIFICATIONS. |
| |
| |
| |
| 2) THIS BUILDING ALSO HAS A FIRE ALARM SYSTEM. |
| |
| THE NEW WALLS REQUIRE A REVIEW OF THE EXISTING FIRE |
| ALARM DEVICES FOR CODE COMPLIANT PROTECTION BY A FIRE |
| ALARM CONTRACTOR. |
| |
| ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER |
| SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE A LETTER OF REVIEW AND |
| COMPLIANCE FROM A FIRE ALARM CONTRACTOR OR PROVIDE A |
| NOTE OF ACKNOWLEDGEMENT THAT A SEPARATE PERMIT WILL BE |
| SUBMITTED WITH SHOP DRAWINGS FOR THE FIRE ALARM |
| MODIFICATIONS. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |