Plan Review Notes For Permit 21030228 |
Permit Number |
21030228 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-09 16:03:07 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21030228 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SEE FIRE REVIEWERS COMMENTS. | | | | 2) PLEASE PROVIDE A GREASE DUCT DRAWING SHOWING THE | | SIZE OF THE DUCTS AND THE ROUTE OF THE DUCTS FROM THE | | HOODS AND DISHWASHER TO THE TERMINATION POINT ON THE | | ROOF. FBC 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|