Plan Review Notes For Permit 21030228 |
Permit Number |
21030228 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-09 11:08:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE SUBMITTED PALN ARE GENERAL IN NATURE AND DO NOT | | APPEAR | | | | 1) THERE IS NO ADDRESS INDICATED IN THE TITLE BLOCK, | | ONLY A OCCUPANCY NAME. | | | | PLEASE CORRECT WITH THE SPECIFIC ADDRESS. | | | | | | 2) THERE IS NO FLOOR PLAN SHOWING THE LOCATION OF THE | | PROPOSED HOOD SYSTEM | | | | PLEASE PROVIDE A FLOOR WITH THE LOCATION OF THE HOOD. | | | | | | 3) THERE IS NO ROOF PLAN INDICATING THE SPECIFIC | | LOCATION OF THE UNIT AND DIMESIONS TO OTHER EQUIPMENT | | OF ROOF LINES | | | | PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF ALL | | EQUIPMENT. | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|