Plan Review Notes
Plan Review Notes For Permit 21030173
Permit Number 21030173
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-05 14:33:161ST REVIEW FBC-2020 RES.
 PERMIT-21030173
 4/5/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LP TANK ANCHORAGE DETAIL HAS A COPIED ENGINEER'S
 SEAL. DOCUMENTS PREPARED BY A FL. LICENSED ENGINEER
 REQUIRE AN ORIGINAL SIGNATURE AND SEAL IS REQUIRED.
 ENGINEERED DOCUMENTS SUBMITTED ELECTRONICALLY SHALL
 HAVE BEAR THE DIGITAL SIGNATURE AND SEAL OF THE FL.
 LICENSED ENGINEER- FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FAC.
  
 2) PLEASE SUBMIT THE SPECS FOR THE 32 KW GENERATOR. THE
 SUBMITTED SPECS ARE FOR SMALLER KW GENERATORS- SECTION
 G2408.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  