Plan Review Notes
Plan Review Notes For Permit 21030170
Permit Number 21030170
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-11 14:32:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REVISE THE NOTE ON THE SURVEY. THE GENERATOR EXHAUST
 IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS TO A
 BUILDING. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) SUBMIT A MIAMI-DADE OF FLORIDA PRODUCT APPROVAL OR
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE
 PRE-FABRICATED GENERATOR PAD. THE SIZE DIMENSIONS AND
 WEIGHT OF THE GENERATOR MUST MATCH THE ONES ON THE
 ENGINEERING OR PRODUCT APPROVAL. THE GENERATOR PAD
 DRAWINGS THAT WERE SUBMITTED DO NOT MATCH THE GENERATOR
 SPECIFICATIONS FOR SIZE AND WEIGHT. FBC AMENDMENTS
 107.2.1
  