2021-04-07 07:24:38 | 2ND REVIEW FBC-2020 RES. FUEL GAS | | PERMIT- 21030166 | | 4/7/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) POOL HEATER SPECS HAVE BEEN SUBMITTED WHICH HAVE | | BEEN HIGHLIGHTED TO SHOW A 399,000 BTU UNIT. PLEASE ADD | | THE BRANCH LINE TO THE HEATER ON THE RISER DRAWING AND | | SHOW THE LOCATION ON THE FLOOR PLAN- SECTION G2413.2 | | FBC RES. | | | | 2) 2ND REQUEST TO PLACE A NOTE ON THE FLOOR PLAN TO | | INDICATE THE GENERATOR (UNDER SEPARATE PERMIT) WILL BE | | INSTALLED A MINIMUM OF 10 FT. FROM OPENINGS INTO THE | | BUILDING- SECTION R303.5 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|