2021-03-18 10:54:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21030128 |
| ADD: 1801 S. FLAGLER DR. # 1608 |
| CONT: COUNIHAN CONSTRUCTION LLC |
| TEL: 561-722-6266 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: |
| ACTION: DENIED |
| |
| 1) SHEET A-1 THE FLOOR PLAN INDICATES NEW FLOORING |
| THROUGHOUT, TO BE DETERMINED. A SALES BROCHURE FOR |
| WHISPER MAT CS FOR CERAMIC TILE. WHEN THE FLOOR PLAN |
| STATES TO BE DETERMINED, THIS BECOMES AN UNKNOWN |
| BECAUSE THE SUBMITTED BROCHURE IS FOR A SPECIFIC TYPE |
| OF MATERIAL. |
| |
| 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES " THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION AND OR TBD". CONSTRUCTION DOCUMENTS SHALL |
| BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE B FLOOR INSULATION (FBC-B 2020) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723.UILDING OFFICIAL. |
| |
| 2) DISCREPANCY IN THE SCOPE OF WORK. ON THE FLOOR PLAN |
| SHEET A-1 THE GENERAL NOTE # 6 STATES NO EXTERIOR |
| ENVELOPE WORK. THE PERMIT APPLICATION UNDER THE |
| DESCRIPTION OF WORK STATES, REMODEL PER PLAN INCLUDING |
| EXTERIOR WINDOW AND SLIDING DOORS. THERE IS NO PRODUCT |
| APPROVAL FOR THE SLIDING GLASS DOORS. THERE IS |
| SUBMITTED WITHIN THIS PERMIT PACKAGE |
| PRODUCT APPROVALS WITH THE DESIGNERS ELECTRONIC |
| SIGNATURE FOR NOA 20-0722.09 CGI WINDOWS. SENTINEL 110 |
| SINGLE HUNG WINDOWS L. M. I. & NOA 20-0406.08 CGI HEAVY |
| DUTY TUBE MULLIONS. NEITHER REPORT HAS SHOWN COMPLIANCE |
| WITH THE 2020 FBC-B SECTION 1405.13.1. PLEASE IDENTIFY |
| ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER |
| OF RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 3) 2020 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| |
| 3,1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 3.2. RISK CATEGORY. |
| |
| 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 3.6.1. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 3.6.2. THERE IS NO OVERALL FLOOR PLAN FOR THE TOTAL |
| FLOOR AREA OF THIS FLOOR, ZONES 4 & 5 NEED TO BE |
| ESTABLISHED. |
| |
| 4) COMPONENTS & CLADDING. 2020 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A) |
| EXTERIOR SLIDING DOORS |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |