2021-04-05 10:55:31 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| REF: COVER PAGE FOR THE FOLLOWING: |
| |
| 1. CHANGE BUILDING OCCUPANCY AND USE FROM R-1 TO R-3. |
| 310.5RESIDENTIAL GROUP R-3. |
| RESIDENTIAL GROUP R-3 OCCUPANCIES WHERE THE OCCUPANTS |
| ARE PRIMARILY PERMANENT IN NATURE AND NOT CLASSIFIED AS |
| GROUP R-1, R-2, R-4 OR I, INCLUDING: |
| |
| 2. CHANGE BUILDING DESIGN CODE REFERENCES TO - 2020 FBC |
| 7TH ED. SOW IS ALTERATION LEVEL II. |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| 2020 FBC 7TH ED - BUILDING |
| 2020 FBC 7TH ED - RESIDENTIAL |
| 2020 FBC 7TH ED - EXISTING |
| 2020 FBC 7TH ED - MECHANICAL |
| 2020 FBC 7TH ED ? PLUMBING/FUEL GAS |
| |
| REF: PLAN PAGE A-1 FOR THE FOLLOWING: |
| |
| 3. PER DETAIL A/A1: |
| 3A) PROVIDE LOCATION OF NEW 24X24X12 CONC BASE OR |
| BASES. |
| |
| 3B) PROVIDE STRUCTURAL REINFORCING FOR CONC BASE. |
| |
| 3C) PROVIDE STRUCTURAL CONNECTION DETAIL FOR NEW CONC |
| BASE TO EXISTING CONC SLAB. |
| |
| 3D) PROVIDE DETAIL FOR METAL RUNNER TO TRUSS CORD PER |
| ENG NOTE. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| REF: FLOOR FRAMING PLAN FOR THE FOLLOWING: |
| |
| 4. FLOOR FRAMING PLAN: |
| 4A) PROVIDE DETAIL OF NEW 6X6 POST'S. |
| |
| 4B) PROVIDE DETAIL OF THE FIVE POST SHOWN ON PLAN. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 5. PROVIDE PRODUCT APPROVALS FOR NEW WINDOW. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |