2021-03-04 15:27:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SITE PLAN DOES NOT CLEARLY SHOW THAT THE GENERATOR
 EXHAUST IS 10 FEET FROM OPENINGS INTO THE BUILDING.
 SHOW COMPLIANCE WITH FBC-R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) PROVIDE GENERATOR TO PAD ANCHORING DETAILS TO SHOW
 HOW THE GENERATOR WILL RESIST WIND LOADS. FBC 107.2.1
  