Notes |
Date |
Text |
2021-03-04 15:27:32 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SITE PLAN DOES NOT CLEARLY SHOW THAT THE GENERATOR | | EXHAUST IS 10 FEET FROM OPENINGS INTO THE BUILDING. | | SHOW COMPLIANCE WITH FBC-R303.5.1 INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | 2) PROVIDE GENERATOR TO PAD ANCHORING DETAILS TO SHOW | | HOW THE GENERATOR WILL RESIST WIND LOADS. FBC 107.2.1 | | |
|