2021-07-16 12:47:56RESIDENTIAL(R3) ELEVATION CERTIFICATE. THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 ORIGINAL COMMENT:
 3- - ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN
 ON ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE TO REVISED SUBMITTAL:
 COMMENT FOR ITEM C2:E STATES "A/C EQUIPMENT PAD".
 ACCORDING TO PHOTOS SUBMITTED, THE A/C EQUIPMENT IS NOT
 MOUNTED ON THE CONCRETE PAD. IT IS MOUNTED ON A/C
 STANDS. THIS NEEDS TO BE CLEARLY IDENTIFIED ON THE
 COMMENTS SECTION.
 NOTE: INFORMATION SHOWN ON SURVEY SUBMITTED IS NOT
 CLEAR ALSO. IT SHOWS 3 ELEVATION MARKS (7.24', 7.27',
 7.30') ON THE CONCRETE SLAB AND ANOTHER LOWER ELEVATION
 (5.65') POINTING TO THE CONCRETE SLAB. WHAT IS THE
 CORRECT CONCRETE PAD ELEVATION?
  
  
  
 REVISE SURVEY SUBMITTED:
  
 ORIGINAL COMMENT:
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE TO REVISED SUBMITTAL:
 REPEAT COMMENT. NOT ADDRESSED. THE FLOOD INFORMATION
 WAS NOT UPDATED.
 FLOOD ZONE A5. COMMUNITY NUMBER: 120229. PANEL:
 1202290020. SUFFIX: B
 IS OLD INFORMATION. SEE SECTION B OF THE ELEVATION
 CERTIFICATE FOR CORRECT UPDATED INFORMATION AND REVISE
 AS REQUIRED.
  
 NEW COMMENTS BASED ON REVISED SURVEY:
 3- SURVEY SUBMITTED NOW SHOWS A NEW BENCHMARK "FOUND
 PK/TAB SITE BENCHMARK ELEVATION =24.40'.
 WHAT IS THE ELEVATION DATUM USED FOR THIS ELEVATION
 24.40'?
 WHYS IS THIS ELEVATION SO HIGH COMPARED TO THE OTHER
 ELEVATIONS SHOWN ON THE SURVEY?
  
 4- INFORMATION SHOWN ON SURVEY SUBMITTED IS NOT CLEAR.
 IT SHOWS 3 ELEVATION MARKS (7.24', 7.27', 7.30') ON THE
 CONCRETE SLAB AND ANOTHER LOWER ELEVATION (5.65')
 POINTING TO THE CONCRETE SLAB.
 WHAT IS THE CORRECT SLAB ELEVATION?
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,