2021-05-18 15:23:49 | RESIDENTIAL(R3) ELEVATION CERTIFICATE. SECOND BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| SUBMITTAL #21030009 (MASTER 16061174). |
| |
| COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON |
| 05/06/2021 FOR MAIN HOUSE: |
| |
| 1- ITEM A3 ON PAGE 1 OF 6 IS INCORRECT. THIS ITEM IS |
| ASKING FOR THE PROPERTY DESCRIPTION. FORM SUBMITTED |
| SAYS 1B. WHAT IS 1B? REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH |
| FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS |
| REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN ON |
| ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY |
| SUBMITTED. REVISE AS REQUIRED. |
| NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND |
| 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT DOESN'T |
| MEET THE CITY FREEBOARD REQUIREMENT OF 1 FOOT ABOVE THE |
| BASE FLOOD ELEVATION AS REQUIRED BY CITY ORDINANCE |
| 4658-16. |
| EQUIPMENT NEEDS TO BE RAISED AND ELEVATION CERTIFICATE |
| NEEDS TO BE REVISED ACCORDINGLY. |
| NOTE: ORIGINAL PLANS WERE APPROVED BEFORE THE NEW FLOOD |
| MAPS TOOK EFFECT. PREVIOUS MAPS WERE BASED ON NGVD 1929 |
| ELEVATION DATUM. BASED ON NGVD, THE BASE FLOOD |
| ELEVATION WAS 7 FEET AND THE REQUIRED FINISHED FLOOR |
| ELEVATION WAS 8 FEET NGVD. |
| |
| 5- COMMENTS ON SECTION D ON PAGE 2 OF 6 SPECIFIES A/C |
| EQUIPMENT PAD LOCATED EASTERLY SIDE OF HOUSE. BASED ON |
| SURVEY SUBMITTED, THIS IS INCORRECT. REVISE AS |
| REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 6- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM |
| C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED |
| BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS. |
| PROVIDE SURVEY SHOWING THOSE ELEVATIONS. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 7- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO |
| BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION. |
| SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019 |
| EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY |
| THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND |
| SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED |
| 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE |
| BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT |
| PHOTOS. |
| NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE |
| AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE |
| YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF |
| CERTIFICATION. |
| |
| |
| COMMENTS FOR ELEVATION CERTIFICATE CERTIFIED ON |
| 05/06/2021 FOR GARAGE: |
| |
| 1- REVISE/CLARIFY DESCRIPTION ON ITEM A4 ON PAGE 1 OF |
| 6. WHAT IS A "DEATTACHED GARAGE"?. REVISE/CLARIFY AS |
| REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- ITEM A7 ON PAGE 1 OF 6 IS INCORRECT. THERE IS NOT |
| CRAWLSPACE IN THE GARAGE. REVISE AS REQUIRED. |
| SEC. 107..2.1 CITY AMENDMENTS. |
| |
| 3- SQUARE FOOTAGE SPECIFIED ON ITEM A8(A) ON PAGE 1 OF |
| 6 IS INCORRECT. ACCORDING TO SURVEY SUBMITTED THE |
| GARAGE SQUARE FOOTAGE IS 733 S.F. NOT 586 S.F. REVISE |
| AS REQUIRED. NOTE: SQUARE FOOTAGE IS TAKEN FROM |
| EXTERIOR WALLS. |
| SEC. 107..2.1 CITY AMENDMENTS. |
| |
| 4- TOTAL NET AREA OF FLOOD OPENINGS SPECIFIED ON ITEM |
| A8(C) ON PAGE 1 OF 6 IS INCORRECT. SURVEYOR PROVIDED |
| COMMENT AT BOTTOM OF SECTION D STATING "VENTING BASED |
| ON FLOOD SOLUTIONS VENTS FS 1412 PER CLIENTS". |
| ACCORDING TO ENGINEERED VENT PRODUCT APPROVAL FL17588 |
| SUBMITTED WITH PERMIT APPLICATION #16061174 THE |
| SELECTED VENT FS-1412 HAS A NET FREE AREA OF 106.7 SQ. |
| IN. PER VENT. IF THERE ARE 5 VENTS, THEN THE TOTAL NET |
| AREA IS 533.5 SQ. IN. NOT 1000 SQ. IN. REVISE AS |
| REQUIRED. NOTE: COORDINATE WITH ITEM #5 BELOW. |
| SEC. 107..2.1 CITY AMENDMENTS. |
| |
| 5- BASED ON ITEMS #3 AND #4 ABOVE IT LOOKS LIKE THE |
| ENGINEER OF RECORD FOR PERMIT #16061174 NEEDS TO REVISE |
| THE PLANS AND NUMBER OF REQUIRED FLOOD VENTS. SHEET A-2 |
| SPECIFIES A GARAGE AREA OF 586 S.F. ALSO, ENGINEER |
| SHOWS 5 FLOOD VENTS (MODEL FS-1412 PRODUCT APPROVAL |
| FL17588) ON WEST AND EAST WALLS. |
| ENGINEER OF RECORD NEEDS TO PROVIDE CORRECT GARAGE |
| SQUARE FOOTAGE AND REVISE THE NUMBER OF REQUIRED VENTS. |
| SUBMIT REVISE PLANS FOR REVIEW. REVISION FEES APPLY. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: SQUARE FOOTAGE IS TAKEN FROM EXTERIOR WALLS. |
| |
| 6- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH |
| FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS |
| REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 7- ITEM C2(B) SHOWN ON PAGE 2 OF 6 IS INCORRECT. THERE |
| IS NOT NEXT HIGHER FLOOR IN THE GARAGE. REVISE AS |
| REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 8- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM |
| C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED |
| BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS. |
| PROVIDE SURVEY SHOWING THOSE ELEVATIONS. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 9- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO |
| BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION. |
| SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019 |
| EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY |
| THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND |
| SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED |
| 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE |
| BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT |
| PHOTOS. |
| NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE |
| AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE |
| YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF |
| CERTIFICATION. |
| |
| |
| REVISE SURVEY SUBMITTED: |
| |
| 1- SURVEY SUBMITTED IS AN SPECIFIC PURPOSE |
| SURVEY-"NORTHERLY FORMBOARDTIE IN". SEE TOP OF SURVEY. |
| IF THIS SURVEY IS FOR ELEVATION CERTIFICATE FINISHED |
| CONSTRUCTION, THEN THE SURVEY SHOULD BE A FINAL SURVEY |
| AS WELL NOT A FORMBOARD SURVEY. PROVIDE FINAL SURVEY. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM |
| MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO |
| EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS |
| REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- SURVEY DOESN'T MATCH APPROVED PLANS AND PHOTOS SHOWN |
| ON THE ELEVATION CERTIFICATES. THERE IS A BREEZEWAY |
| CONNECTING THE GARAGE TO THE MAIN HOUSE. REVISE AS |
| REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- PROVIDE REVISED SURVEY WITH SURVEYORS ORIGINAL |
| SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN |
| SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| NOTE: THIS CAN BE ACHIEVED BY UPLOADING DOCUMENTS WITH |
| SURVEYOR'S DIGITAL SIGNATURE OR BY PROVIDING HARD COPY |
| PLANS/DOCUMENTS WITH SURVEYOR'S ORIGINAL |
| SEAL/SIGNATURE. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |