Plan Review Notes
Plan Review Notes For Permit 21021430
Permit Number 21021430
Review Stop E
Sequence Number 4
Notes
Date Text
2022-11-01 14:58:15ELECTRIC REVIEW FAILED
 1) IT APPEARS GUEST COTTAGE DETAILS MORE THAN ONE MULTI
 WIRE CIRCUIT. PLEASE INDICATE THAT GUEST HOUSE HAS
 SUBPANEL FOR GUEST HOUSE LOADS. AS PER NEC 225.30
 IN ADDITION, SINCE THIS GUEST HOUSE APPEARS IT WILL
 REQUIRE AN ELECTRIC SUB PANEL, INDICATE THE NECESSARY
 GROUNDING ELECTRODE SYSTEM AS PER NEC 250.32
 2) PROVIDE AN ELECTRICAL RISER DIAGRAM DETAILING ALL
 ELECTRIC EQIPMENT, METERS PANELS, CONDUIT ANND
 CONDUCTOR SIZES AS NEC 215.5
 3) PLEASE PROVIDE LOAD CALCULATIONS FOR ALL
 DISTRIBUTION PANELS NEC 220
 4) PLEASE LOCATE ALL ELECTRIC EQUIPMENT ON A SITE PLAN
 FBC 107.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  