Plan Review Notes
Plan Review Notes For Permit 21021430
Permit Number 21021430
Review Stop M
Sequence Number 3
Notes
Date Text
2022-02-16 15:09:21THE HVAC LOAD CALCULATIONS AND THE MECHANICAL DRAWING
 DO NOT MATCH. PLEASE SUBMIT DOCUMENTS THAT MATCH EACH
 OTHER. THE LOAD CALCULATIONS MENTION HYDRONIC BASEBOARD
 HEAT BUT THERE IS NOTHING ON THE MECHANICAL DRAWING
 ABOUT THIS. THE LOAD CALCULATIONS SHOW 11979 BTUH BUT
 THE MECHANICAL DRAWING SHOWS A 2-TON UNIT. THE LOAD
 CALCULATIONS SHOW THAT A ZONED SYSTEM MUST BE INSTALLED
 BECAUSE OF THE LARGE SPIKES IN SOLAR LOAD BUT THE
 DRAWING SHOWS A 1 ROOM STRUCTURE WITHOUT A ZONED
 SYSTEM.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER