Plan Review Notes For Permit 21021430 |
Permit Number |
21021430 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-02-16 15:09:21 | THE HVAC LOAD CALCULATIONS AND THE MECHANICAL DRAWING | | DO NOT MATCH. PLEASE SUBMIT DOCUMENTS THAT MATCH EACH | | OTHER. THE LOAD CALCULATIONS MENTION HYDRONIC BASEBOARD | | HEAT BUT THERE IS NOTHING ON THE MECHANICAL DRAWING | | ABOUT THIS. THE LOAD CALCULATIONS SHOW 11979 BTUH BUT | | THE MECHANICAL DRAWING SHOWS A 2-TON UNIT. THE LOAD | | CALCULATIONS SHOW THAT A ZONED SYSTEM MUST BE INSTALLED | | BECAUSE OF THE LARGE SPIKES IN SOLAR LOAD BUT THE | | DRAWING SHOWS A 1 ROOM STRUCTURE WITHOUT A ZONED | | SYSTEM. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|