2021-10-18 12:36:16 | 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-21021430 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW |
| STRUCTURE AS REQUESTED IN THE FIRST REVIEW COMMENTS. |
| FBC EC 101.5.1.1.2 |
| |
| 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS AS REQUESTED IN THE FIRST REVIEW COMMENTS. |
| FBC EC R403.7.1 |
| |
| 3) SHEET M-1 SHOWS A MINI-SPLIT ONLY AND ONLY A FIRST |
| FLOOR. S1-3 INDICATES DUCTWORK FOR THE FIRST AND SECOND |
| FLOOR BUT DOES NOT SHOW THE MECHANICAL SYSTEM. PLEASE |
| PROVIDE MECHANICAL DRAWINGS THAT ARE CONSISTENT AND |
| PROVIDE DETAILS FOR THE MECHANICAL SYSTEM. INCLUDING |
| THE LOCATION OF THE AHU AND THE CONDENSING UNIT ALONG |
| WITH THE ANCHORING DETAILS OF THE CONDENSING UNIT. |
| PLEASE ALSO SHOW THE CONDENSATE PIPING AND TERMINATION |
| LOCATION. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |