Plan Review Notes For Permit 21021430 |
Permit Number |
21021430 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-11-08 12:42:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | DISCONNECT, PANEL, AND GROUNDING REQUIRED 225.30, | | 225,31, 225,32 | | | | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | FEEDER OR BRANCH CIRCUIT. NEC 225.30 | | | | PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC | | | | |
|