2021-03-18 11:00:40CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 PERMIT: 21021430- ELECTRICAL REVIEW
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SHEET S1-1: ELECTRICAL NOTES MENTION TO ADD
 ELECTRICAL TO EXISTING ELECTRICAL PANEL. PLEASE SHOW
 LOCATION OF THIS EXISTING ELECTRICAL PANEL. IS THE
 EXISTING PANEL LOCATED AT THE MAIN RESIDENCE OR IS THIS
 A SUBPANEL AT THE NEW STORAGE UNIT? IF THIS IS A
 SUBPANEL LOCATED AT THE STORAGE UNIT, PLEASE PROVIDE A
 RISER DIAGRAM SHOWING MAIN PANEL AND SUBPANEL WITH
 FEEDER SIZES AND GROUNDING DETAILS. FBC 107
 2) IT SEEMS THAT IN ADDITION TO THE LIGHTS AND
 RECEPTACLES BEING INSTALLED THERE IS ALSO AN HVAC UNIT.
 PLEASE SHOW DISCONNECT, ELECTRICAL CIRCUIT FOR THIS
 UNIT, SPECIFY CONDUCTOR SIZES. PLEASE SHOW LOCATION OF
 THE HVAC UNIT. FBC 107
 3) GFCI/WP RECEPTACLE REQUIRED FOR HVAC UNIT. SHOW
 LOCATION OF THIS RECEPTACLE. NEC 210.63
 4) PLEASE PROVIDE A PANEL SCHEDULE OF THE EXISTING
 PANEL SHOWING THE CIRCUITS FOR NEW STORAGE UNIT.
 INCLUDE PANEL RATINGS AND MCB SIZE. FBC 107
 5) RECEPTACLE IN BATHROOM MUST BE GFCI TYPE. NEC
 210.8(A)(1)
 6) ALL RECEPTACLES IN ACCESSORY UNIT (STORAGE ROOM)
 MUST BE GFCI TYPE. NEC 210.8(A)(2)
 7) PLEASE INCLUDE LIST OF ELECTRICAL SYMBOLS BEING
 USED. FBC 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved