| PERMIT: 21021430- ELECTRICAL REVIEW |
| |
| REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| |
| 1) SHEET S1-1: ELECTRICAL NOTES MENTION TO ADD |
| ELECTRICAL TO EXISTING ELECTRICAL PANEL. PLEASE SHOW |
| LOCATION OF THIS EXISTING ELECTRICAL PANEL. IS THE |
| EXISTING PANEL LOCATED AT THE MAIN RESIDENCE OR IS THIS |
| A SUBPANEL AT THE NEW STORAGE UNIT? IF THIS IS A |
| SUBPANEL LOCATED AT THE STORAGE UNIT, PLEASE PROVIDE A |
| RISER DIAGRAM SHOWING MAIN PANEL AND SUBPANEL WITH |
| FEEDER SIZES AND GROUNDING DETAILS. FBC 107 |
| 2) IT SEEMS THAT IN ADDITION TO THE LIGHTS AND |
| RECEPTACLES BEING INSTALLED THERE IS ALSO AN HVAC UNIT. |
| PLEASE SHOW DISCONNECT, ELECTRICAL CIRCUIT FOR THIS |
| UNIT, SPECIFY CONDUCTOR SIZES. PLEASE SHOW LOCATION OF |
| THE HVAC UNIT. FBC 107 |
| 3) GFCI/WP RECEPTACLE REQUIRED FOR HVAC UNIT. SHOW |
| LOCATION OF THIS RECEPTACLE. NEC 210.63 |
| 4) PLEASE PROVIDE A PANEL SCHEDULE OF THE EXISTING |
| PANEL SHOWING THE CIRCUITS FOR NEW STORAGE UNIT. |
| INCLUDE PANEL RATINGS AND MCB SIZE. FBC 107 |
| 5) RECEPTACLE IN BATHROOM MUST BE GFCI TYPE. NEC |
| 210.8(A)(1) |
| 6) ALL RECEPTACLES IN ACCESSORY UNIT (STORAGE ROOM) |
| MUST BE GFCI TYPE. NEC 210.8(A)(2) |
| 7) PLEASE INCLUDE LIST OF ELECTRICAL SYMBOLS BEING |
| USED. FBC 107 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| MS |
| |
| ENRIQUE QUINONEZ P.E. |
| ELECTRICAL PLANS EXAMINER |
| DEVELOPMENT SERVICES |
| CITY OF WEST PAM BEACH |
| 401 CLEMATIS STREET, 1ST FLOOR |
| WEST PALM BEACH, FL 33401 |
| |
| FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, |
| 561-805-6746. |
| |