Plan Review Notes
Plan Review Notes For Permit 21021410
Permit Number 21021410
Review Stop M
Sequence Number 2
Notes
Date Text
2021-03-18 09:43:27THE AIR BALANCE REPORT SUBMITTED DATED MARCH 10,2021 IS
 NOT FROM THE ENGINEER THAT ORIGINALLY SUBMITTED THE AIR
 BALANCE SCHEDULE ON SHEET 1 OF 7 OF THE DRAWINGS.
 NEITHER AIR BALANCE REPORTS INCLUDES THE BATHROOM
 EXHAUST FANS. THE BATHROOM EXHAUST FANS MUST BE
 INCLUDED IN THE AIR BALANCE REPORT.
  
 FBC M 508.1.2AIR BALANCE.
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION.
  