2021-04-22 08:14:12 | 04/22/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER |
| THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| DRYERS). IF LOUVER WILL BE USED. PLEASE SHOW THE |
| LOCATION AND SIZE OF THE LOUVER(S) ON THE PLANS PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| |
| 3. PLEASE SHOW THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| |
| 5. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC |
| RES. SEC. G2413. |
| |
| 6. PLEASE SHOW THE DISTANCE FROM THE POINT OF DELIVERY |
| (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| RES. SEC. G2413.4.1. |
| |
| 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| FBC RES. SEC. G2413.2 AND G2404.3. |
| |
| 8. THE GAS GRILL AND IT SEEMS TO BE IN A COVERED PATIO, |
| IF SO PLEASE PROVIDE THE MANUFACTURE'S RECOMMENDATION |
| FOR A VENTILATION HOOD PER THE 2020 FBC RES. SEC. |
| G2408.1. |
| |
| 9. NEED A HARD CAP FOR FUTURE RANGE SHOW ON GAS |
| ISOMERIC PER THE 2020 FBC RES. SEC. G2401.1.3. |
| |
| 10. IF THIS UNIT REQUIRES A CONDENSATE, IT WILL NEED TO |
| BE 1' AWAY FROM STRUCTURE PER THE 2020 FBC SEC R318.5. |
| |
| 11. PLEASE SHOW THE LOCATION OF THE TANK-LESS WATER |
| HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE |
| DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE |
| LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 12. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC |
| G2421.2. |
| |
| 13. PLEASE LABEL THE SHUT-OFF VALVE ON GAS ISOMERIC AND |
| THEY SHALL HAVE ACCESS TO THEM PER THE 2020 FBC RES. |
| SEC. G2420.5. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |