2021-03-19 06:40:03 | 03/19/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. ON PAGE A-1L; |
| A. IT SHOWS A GAS TANK-LESS. PLEASE PROVIDE A NOTE ON |
| PLANS THAT A SEPARATE PERMIT SHALL BE SUBMITTED FOR GAS |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| B. THE TANKLESS HOT WATER LINES ON THE OUTSIDE SHALL |
| HAVE INSULATED MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| 403.5.3. PLEASE PLACE A NOTE. |
| |
| C. IF THIS HAS A CONDENSATE, IT WILL NEED TO BE 1' AWAY |
| FROM THE STRUCTURE PER THE 2017 FBC SEC. R318.5. |
| |
| D. PLEASE SHOW THE TANK-LESS WATER HEATER'S LOCATION |
| AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| |
| 3. ON SHEET S1L AND S1R; |
| A. THE LAUNDRY TRAY IS NOT SHOW NEXT TO WASHING |
| MACHINE. |
| |
| B. IN BATH THREE THE SINK IS NOT SIZED. |
| |
| PLEASE CORRECT THESE ITEMS PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |