Plan Review Notes
Plan Review Notes For Permit 21021356
Permit Number 21021356
Review Stop M
Sequence Number 1
Notes
Date Text
2021-04-30 09:30:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21021356
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE BUILDING REVIEWER COMMENTS.
  
 2) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS
 GENERATOR INSTALLATION.
  
 3) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN
 THE GENERATOR ROOM. PLEASE INCLUDE THE EXHAUST DETAILS
 OF THE GENERATOR INCLUDING LOCATION OF THE TERMINATION
 AND HEIGHT IT IS EXITING THE BUILDING. FBC 107.2.1; FBC
 M 607
  
 4) PLEASE SHOW THE PROPERTY LINES AND DISTANCE AWAY
 FROM PROPERTY LINES FOR THE GENERATOR EXHAUST. FBC M
 501.3.1
  
 5) PLEASE SHOW THE METHOD OF TANK FILL FOR THE DIESEL
 FUEL TANK. FBC M 1305.6
  
 6) PLEASE PROVIDE A DETAIL FUEL PIPING DRAWING
 INDICATING THE PIPING TYPE AND SIZES. FBC M 1305
  
 7) PLEASE SOW THE VENT PIPING FOR THE TANK AND THE
 TERMINATION LOCATION. FBC M 1305.7
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  