2021-04-30 09:30:42 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21021356 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SEE BUILDING REVIEWER COMMENTS. |
| |
| 2) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS |
| GENERATOR INSTALLATION. |
| |
| 3) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN |
| THE GENERATOR ROOM. PLEASE INCLUDE THE EXHAUST DETAILS |
| OF THE GENERATOR INCLUDING LOCATION OF THE TERMINATION |
| AND HEIGHT IT IS EXITING THE BUILDING. FBC 107.2.1; FBC |
| M 607 |
| |
| 4) PLEASE SHOW THE PROPERTY LINES AND DISTANCE AWAY |
| FROM PROPERTY LINES FOR THE GENERATOR EXHAUST. FBC M |
| 501.3.1 |
| |
| 5) PLEASE SHOW THE METHOD OF TANK FILL FOR THE DIESEL |
| FUEL TANK. FBC M 1305.6 |
| |
| 6) PLEASE PROVIDE A DETAIL FUEL PIPING DRAWING |
| INDICATING THE PIPING TYPE AND SIZES. FBC M 1305 |
| |
| 7) PLEASE SOW THE VENT PIPING FOR THE TANK AND THE |
| TERMINATION LOCATION. FBC M 1305.7 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |