2022-08-03 15:59:38 | 2ND REVIEW FBC-2017 FUEL GAS |
| PERMIT- 21021355- STANDBY GENERATOR |
| 8/3/2022 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| NFPA 37, 54 & 110 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| CAPS. |
| |
| 3) FAILED. CORRECT SHEET E-407 SHOWING GENERATOR SPECS |
| FOR MTU 4R0063 GS30. THE APPROVED SUBMITTAL UPLOADED IS |
| FOR A CUMMINGS C30 NG- SECTION 107.2.1 WPB AND SECTION |
| 305.1 FBC FG. CORRECTION NOT PROVIDED. |
| |
| 7) FAILED. INDICATE HOW COMBUSTION AIR WILL BE PROVIDED |
| TO THE GENERATOR AND PROVIDE CALCULATIONS- SECTION |
| 304.1 FBC FG. A) SHEET M103: THE COMBUSTION AIR |
| CALCULATIONS SHOW THEY ARE BASED ON 38,500 BTU/HR LOAD |
| HOWEVER THE GENERATOR SPECS INDICATE 389,000 BTU/HR. |
| PLEASE CORRECT. B) M103: PLEASE LABEL THE SUPPLY CFMS |
| AT THE DIFFUSER IN THE GENERATOR ROOM. |
| |
| NEW COMMENTS BASED ON RESUBMITTED PLANS. |
| |
| 1) SHEETS P-101B, P-242, & P-505: THE UPDATED PLAN |
| SHEETS DO NOT MATCH. |
| |
| A) SHEET P-101B SHOWS ONLY ONE METER AND THE PIPE RUNS |
| AND PIPE SIZES DO NOT MATCH THE ENLARGED PIPING LAYOUT |
| DRAWING (P-242) AND THE RISER (P-505. |
| |
| B) P-242 SHOWS A 2-1/2 LOW PRESSURE SUPPLY LINE ON |
| LEVEL 01 FROM THE METER TO THE VERTICAL RISER PIPE, |
| HOWEVER THE ISOMETRIC DRAWING (P-505) SHOWS A 3-INCH |
| PIPE. WHICH IS IT? |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |