2021-04-30 08:37:50 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21021355 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS |
| GENERATOR INSTALLATION. |
| |
| 2) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN |
| THE GENERATOR ROOM. PLEASE IDENTIFY THE INTAKE AIR |
| LOCATION AND INCLUDE THE EXHAUST DETAILS OF THE |
| GENERATOR. THE ORIGINAL APPROVED DRAWINGS DO NOT SHOW |
| THE GENERATOR ROOM INSIDE OF THE MECHANICAL ROOM. THERE |
| IS ELEVATOR PRESSURIZATION DUCT WORK FOR OUTDOOR AIR |
| LOCATED INSIDE OF THIS ROOM. IF THE NEW WALLS FOR THE |
| GENERATOR ROOM ARE REQUIRED TO BE FIRE RATED PLEASE |
| REVISE THE APPROVED DRAWING SHOWING THE RATED WALLS AND |
| THE PROTECTION REQUIRED FOR THE ELEVATOR PRESSURIZATION |
| DUCTWORK. FBC 107.2.1; FBC M 607 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |