Plan Review Notes
Plan Review Notes For Permit 21021355
Permit Number 21021355
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-29 09:29:153RD FLOOR GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A DRAWING THAT SHOWS THE PATH OF THE
 GAS LINE TO COMPLY WITH FBC 403.4.8.2 FUEL LINE PIPING
 PROTECTION.
 FUEL LINES SUPPLYING A GENERATOR SET INSIDE A BUILDING
 SHALL BE SEPARATED FROM AREAS OF THE BUILDING OTHER
 THAN THE ROOM THE GENERATOR IS LOCATED IN BY AN
 APPROVED METHOD OR ASSEMBLY THAT HAS A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 2 HOURS. WHERE THE BUILDING IS
 PROTECTED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2, THE REQUIRED FIRE-RESISTANCE RATING SHALL BE
 REDUCED TO 1 HOUR.