Plan Review Notes
Plan Review Notes For Permit 21021343
Permit Number 21021343
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-17 10:34:501ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21021343
 3/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COVER SHEET: THE PLUMBING FIXTURE CALCULATIONS DO
 NOT INCLUDE THE STORAGE OCCUPANCY CALCULATIONS- TABLE
 403.1 FBC P.
  
 2) A1: PLEASE LABEL THE TOILET ROOMS AS EITHER MALE OR
 FEMALE ACCORDING TO TABLE 403.1 AND 403.2 FBC P.
  
 3) SHEET A-2: SHOW THE HEIGHTS OF THE GRAB BARS FROM
 THE FINISHED FLOORS TO THE TOPS OF THE GRIPPING
 SURFACES- - SECTION 609.4 FBC ACC.
  
 4) A-2: THE REAR GRAB BEHIND THE WATER CLOSET MUST BE
 CENTERED ACCORDING TO SECTION AND FIGURE 604.5.2 FBC
 ACC.
  
 5) A-2: RELOCATE THE WATER CLOSET FLUSH CONTROL TO THE
 OPEN SIDE OF THE WATER CLOSET- SECTION 604.6 FBC ACC.
  
 6) P1: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING
 MAKES, MODELS AND COMPLIANCE STANDARDS- SECTIONS 419,
 422, AND 425 FBC P.
  
 7) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CHRONOMITE WATER HEATER VERIFYING THE UNIT IS ASSE 1070
 LISTED TO PROVIDE TEMPERED WATER TO THE LAVATORIES. IF
 THE UNIT IS NOT ASSE 1070 APPROVED PLEASE PROVIDE A
 MIXING VALVE IN ACCORDANCE WITH SECTION 607.1.2 FBC P.
  
 8) P1: THE WATER RISER SHOWS A COLD WATER LINE TO THE
 EXISTING MOP SINK, HOWEVER HOT WATER IS REQUIRED PER
 SECTION 607.1 FBC P. PLEASE SHOW THE SOURCE OF THE HOT
 WATER.
  
 9) P1: PLEASE REMOVE THE WORD ASSUMED FROM THE SANITARY
 RISER AND PROVIDE COMPLETE WET VENTING DETAILS FOR THE
 NEW ADA TOILET ROOM- SECTION 912.1 FBC P.
  
 10) P1: SHOW IN THE SANITARY RISER THERE IS AN EXISTING
 VENT TO THE OUTDOORS SERVING THE BUILDING DRAIN AS
 REQUIRED BY SECTION 904.1 FBC P.
  
 11) P1: THE NOTE AT BOTTOM LEFT OF THE SHEET CALLS OUT
 TRAP PRIMER VALVE FOR FLOOR DRAIN, HOWEVER NO FLOOR
 DRAIN IS SHOWN IN THE DRAWINGS- PLEASE CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  