2021-03-17 10:34:50 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21021343 |
| 3/17/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) COVER SHEET: THE PLUMBING FIXTURE CALCULATIONS DO |
| NOT INCLUDE THE STORAGE OCCUPANCY CALCULATIONS- TABLE |
| 403.1 FBC P. |
| |
| 2) A1: PLEASE LABEL THE TOILET ROOMS AS EITHER MALE OR |
| FEMALE ACCORDING TO TABLE 403.1 AND 403.2 FBC P. |
| |
| 3) SHEET A-2: SHOW THE HEIGHTS OF THE GRAB BARS FROM |
| THE FINISHED FLOORS TO THE TOPS OF THE GRIPPING |
| SURFACES- - SECTION 609.4 FBC ACC. |
| |
| 4) A-2: THE REAR GRAB BEHIND THE WATER CLOSET MUST BE |
| CENTERED ACCORDING TO SECTION AND FIGURE 604.5.2 FBC |
| ACC. |
| |
| 5) A-2: RELOCATE THE WATER CLOSET FLUSH CONTROL TO THE |
| OPEN SIDE OF THE WATER CLOSET- SECTION 604.6 FBC ACC. |
| |
| 6) P1: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING |
| MAKES, MODELS AND COMPLIANCE STANDARDS- SECTIONS 419, |
| 422, AND 425 FBC P. |
| |
| 7) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| CHRONOMITE WATER HEATER VERIFYING THE UNIT IS ASSE 1070 |
| LISTED TO PROVIDE TEMPERED WATER TO THE LAVATORIES. IF |
| THE UNIT IS NOT ASSE 1070 APPROVED PLEASE PROVIDE A |
| MIXING VALVE IN ACCORDANCE WITH SECTION 607.1.2 FBC P. |
| |
| 8) P1: THE WATER RISER SHOWS A COLD WATER LINE TO THE |
| EXISTING MOP SINK, HOWEVER HOT WATER IS REQUIRED PER |
| SECTION 607.1 FBC P. PLEASE SHOW THE SOURCE OF THE HOT |
| WATER. |
| |
| 9) P1: PLEASE REMOVE THE WORD ASSUMED FROM THE SANITARY |
| RISER AND PROVIDE COMPLETE WET VENTING DETAILS FOR THE |
| NEW ADA TOILET ROOM- SECTION 912.1 FBC P. |
| |
| 10) P1: SHOW IN THE SANITARY RISER THERE IS AN EXISTING |
| VENT TO THE OUTDOORS SERVING THE BUILDING DRAIN AS |
| REQUIRED BY SECTION 904.1 FBC P. |
| |
| 11) P1: THE NOTE AT BOTTOM LEFT OF THE SHEET CALLS OUT |
| TRAP PRIMER VALVE FOR FLOOR DRAIN, HOWEVER NO FLOOR |
| DRAIN IS SHOWN IN THE DRAWINGS- PLEASE CLARIFY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |