2021-03-02 11:24:18 | 03/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE COMPLETE THE PLUMBING APPLICATION AND HAVE |
| THE CONTRACTOR'S LICENSE FOR THE SCOPE OF WORK PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| |
| 2. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| THE MAIN DRAIN AND THE PUMP PER THE WPB AMENDMENTS TO |
| FBC SEC. 107.2.1. |
| |
| 3. PLEASE SUBMIT THE POOL PUMP CURVE. IDENTIFY ON THE |
| PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP |
| BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM |
| THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER |
| THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. |
| |
| 4. SIGNED AND SEALED DRAWINGS NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| ASKING FOR THE FORM. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |