2021-03-30 16:18:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | SUBFEEDER TO BE 3/0 COPPER FOR 200A SUBFEEDER. | | | | 310.15(B)(7)(2) FOR A FEEDER RATED 100 THROUGH 400 | | AMPERES, THE FEEDER CONDUCTORS SUPPLYING THE ENTIRE | | LOAD ASSOCIATED WITH A ONE-FAMILY DWELLING, OR THE | | FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED | | WITH AN INDIVIDUAL DWELLING UNIT IN A TWO-FAMILY OR | | MULTIFAMILY DWELLING, SHALL BE PERMITTED TO HAVE AN | | AMPACITY NOT LESS THAN 83 PERCENT OF THE FEEDER RATING. |
|