Plan Review Notes
Plan Review Notes For Permit 21021175
Permit Number 21021175
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-02 12:17:0603/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS SCOPE OF WORK IS NOT CLEAR. THE CONTRACT HAS
 VERBIAGE THAT IS NOT ON PLAN AND WILL REQUIRE
 ADDITIONAL PERMITS. THIS PERMIT WILL NEED TO BE CHANGED
 TO AN INTERIOR RENOVATION WITH A NEW BUILDING
 APPLICATION AS A MASTER WITH PLUMBING, GAS, MECHANICAL,
 AND ELECTRICAL AS SUBS. PLEASE GET WITH THE PERMIT
 LIBRARIAN TO MAKE THESE CHANGES.
  
 2. THE CONTRACT STATES A KITCHEN HOOK UP. PLEASE
 SPECIFY IF THIS IS AN OUTSIDE KITCHENETTE. IT ALSO SAYS
 AN OUTDOOR SHOWER; PLEASE PROVIDE A COMPLETE SET OF
 PLANS THAT SHOW THE WORK SCOPE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THE WASHING MACHINE THAT WILL BE INSTALLED USALLY
 COMES WITH A DRYER. THESE ITEMS REQUIRE ELECTRICAL AND
 MECAHINAL HOOK UP; PLEASE PROVIDE A COMPLETE SET OF
 PLANS THAT SHOW THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. HOT WATER PIPES NOT IN CONDITION SPACE OR OUTSIDE
 WILL NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE
 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720