2021-03-02 12:17:06 | 03/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THIS SCOPE OF WORK IS NOT CLEAR. THE CONTRACT HAS |
| VERBIAGE THAT IS NOT ON PLAN AND WILL REQUIRE |
| ADDITIONAL PERMITS. THIS PERMIT WILL NEED TO BE CHANGED |
| TO AN INTERIOR RENOVATION WITH A NEW BUILDING |
| APPLICATION AS A MASTER WITH PLUMBING, GAS, MECHANICAL, |
| AND ELECTRICAL AS SUBS. PLEASE GET WITH THE PERMIT |
| LIBRARIAN TO MAKE THESE CHANGES. |
| |
| 2. THE CONTRACT STATES A KITCHEN HOOK UP. PLEASE |
| SPECIFY IF THIS IS AN OUTSIDE KITCHENETTE. IT ALSO SAYS |
| AN OUTDOOR SHOWER; PLEASE PROVIDE A COMPLETE SET OF |
| PLANS THAT SHOW THE WORK SCOPE PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. THE WASHING MACHINE THAT WILL BE INSTALLED USALLY |
| COMES WITH A DRYER. THESE ITEMS REQUIRE ELECTRICAL AND |
| MECAHINAL HOOK UP; PLEASE PROVIDE A COMPLETE SET OF |
| PLANS THAT SHOW THE SCOPE OF WORK PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 5. HOT WATER PIPES NOT IN CONDITION SPACE OR OUTSIDE |
| WILL NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE |
| 2017 FBC SEC. RE 403.5.3. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |