2021-03-02 12:36:12 | 03/02/21 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| EXISTING GAS. A COMPLETE EVALUATION OF ALL GAS |
| EQUIPMENT WILL BE DONE AT THE FIELD; IF NOT TO CODE, IT |
| MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT THE |
| OWNER'S EXPENSE. |
| |
| 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 6. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER |
| THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR PER THE 2020 FBC RES. SEC. |
| G2420.4. |
| |
| 8. THIS TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| G2421.1. |
| |
| 9. ARE THERE ANY OTHER GAS APPLIANCES ARE? IF SO? |
| PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC |
| RES. SEC. G2413. |
| |
| 10. PLEASE PROVIDE THE DISTANCE FROM THE POINT OF |
| DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| THE 2020 FBC RES. SEC. G2413.4.1. |
| |
| 11. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE |
| SYSTEM ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| |
| 12. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL ( IF APPLICABLE RANGE, |
| DRYER, BBQ GRILL) FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| |
| 13. ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| FBC RES. SEC. G2413.2 AND G2404.3. |
| |
| 14. PLEASE INDICATE ON THE PLAN IF THE GRILL IS LOCATED |
| UNDER A ROOF PER THE WPB AMENDMENTS TO FBC SEC. |
| 107.2.1. |
| |
| 15. IF THE GAS GRILL IS LABELED FOR OUTDOOR USE AND IT |
| WILL BE IN A COVERED PATIO, IF THIS IS SO, PLEASE |
| PROVIDE MANUFACTURES RECOMMENDATION FOR A VENTILATION |
| HOOD PER THE 2017 FG 305.1 OR 2017 FBC RES. SEC. |
| G2408.1. |
| |
| 16. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN |
| THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH |
| SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES |
| OR ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM |
| PER THE 2020 FBC RES. SEC. G2413.3. |
| |
| 17. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE, SHUTOFF VALVES, AND DRIP |
| LEG PER THE 2020 FBC RES. SEC G2421.2. |
| |
| 18. PLEASE SUBMIT A HOUSE PLAN THAT SHOWS THE TANK-LESS |
| WATER HEATER'S LOCATION AND THE LOCATION AND DISTANCE |
| OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE |
| WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL |
| COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 19. IF GAS TANKLESS UNITS REQUIRE CONDENSATEDRAIN IT |
| WILL NEED TO BE 1' AWAY FROM STRUCTURE PER THE 2020 FBC |
| SEC R318.5. |
| |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |