Plan Review Notes For Permit 21020965 |
Permit Number |
21020965 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-28 09:22:33 | 05/28/21 1ST POOL PLUMBING REVIEW**DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON THE SHEETS, SP1 UNDER POOL SPECS AND IN E101 | | UNDER PIPING SCHEMATICS DO NOT SHOW THE HEAT PUMP. | | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|