Plan Review Notes
Plan Review Notes For Permit 21020896
Permit Number 21020896
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-23 08:50:161ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020896
 3/23/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P.1 & P.2: NO SIZING CALCULATIONS HAVE BEEN
 PROVIDED FOR THE GREASE WASTE LINE AND FUTURE GREASE
 INTERCEPTOR. INSTALLATION OF THE 3-INCH GREASE WASTE
 LINE WILL BE AT THE BUILDING OWNER'S AND CONTRACTOR'S
 RISK- SECTION 107.2.1 WPB.
  
 A) NOTE J INDICATES THE POINT OF CONNECTION OF THE
 GREASE WASTE LINE TO THE EXISTING BUILDING SEWER,
 HOWEVER THIS CONNECTION CANNOT BE MADE UNTIL THE FUTURE
 INTERCEPTOR IS INSTALLED. PLEASE REVISE THE NOTE TO
 INDICATE "FUTURE POINT OF CONNECTION"- SECTION 107.2.1
 WPB.
  
 B) SHOW A TWO-WAY CLEANOUT AT THE JUNCTION OF THE DRAIN
 LINE AND SEWER JUNCTION- SECTIONS 708.1.3 & 708.1.8 FBC
 P.
  
 2) P.1 & P.2: NOTE G INDICATES THE SANITARY LINES ABOVE
 THE CEILING WHICH APPEARS TO BE INCORRECT. DOES THE
 BUILDING HAVE A SECOND STORY? IF SO PLEASE PROVIDE A
 NOTE AND SYMBOL TO CLARIFY- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  