2021-03-23 08:50:16 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21020896 |
| 3/23/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P.1 & P.2: NO SIZING CALCULATIONS HAVE BEEN |
| PROVIDED FOR THE GREASE WASTE LINE AND FUTURE GREASE |
| INTERCEPTOR. INSTALLATION OF THE 3-INCH GREASE WASTE |
| LINE WILL BE AT THE BUILDING OWNER'S AND CONTRACTOR'S |
| RISK- SECTION 107.2.1 WPB. |
| |
| A) NOTE J INDICATES THE POINT OF CONNECTION OF THE |
| GREASE WASTE LINE TO THE EXISTING BUILDING SEWER, |
| HOWEVER THIS CONNECTION CANNOT BE MADE UNTIL THE FUTURE |
| INTERCEPTOR IS INSTALLED. PLEASE REVISE THE NOTE TO |
| INDICATE "FUTURE POINT OF CONNECTION"- SECTION 107.2.1 |
| WPB. |
| |
| B) SHOW A TWO-WAY CLEANOUT AT THE JUNCTION OF THE DRAIN |
| LINE AND SEWER JUNCTION- SECTIONS 708.1.3 & 708.1.8 FBC |
| P. |
| |
| 2) P.1 & P.2: NOTE G INDICATES THE SANITARY LINES ABOVE |
| THE CEILING WHICH APPEARS TO BE INCORRECT. DOES THE |
| BUILDING HAVE A SECOND STORY? IF SO PLEASE PROVIDE A |
| NOTE AND SYMBOL TO CLARIFY- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |