Plan Review Notes For Permit 21020874 |
Permit Number |
21020874 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-21 13:51:33 | STAIR SHOP DRAWINGS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) EXTERIOR STAIR IS SUBJECT TO WIND LOADS- PLEASE SHOW | | THE WIND DESIGN CRITERIA TO COMPLY WITH FBC 1603.1.4 | | 2) PLEASE PROVIDE THE STRUCTURAL CALCULATIONS FOR THE | | STAIR DESIGN OR HAVE THE DRAWINGS SIGNED AND SEALED BY | | A DESIGN PROFESSIONAL. FBC 107.2.1.2 | | 3) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER AND SHOW | | THE PRINTED NAME FBC 107.2.1 - FBC 107.1 | | 4) INTERIOR STAIR DRAWING NEEDS TO SHOW THE ATTACHMENTS | | TO THE STRUCTURE. FBC 107.2.1 |
|