2021-03-02 17:35:13 | RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| |
| PERMIT #21020831 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| |
| 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL4930-R14 |
| SUBMITTED IS FOR THE 2017 CODE VERSION. AS OF DECEMBER |
| 31, 2020, THE CURRENT CODE IS THE 2020 VERSION (SEC. |
| 553 F.S.). PROVIDE PRODUCT APPROVAL FOR THE CURRENT |
| CODE VERSION AND CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. 1609.1 FBC-BUILDING. |
| |
| 2- NOTE: SEPARATE PERMIT FOR MECHANICAL ROOFING |
| EQUIPMENT MAY BE REQUIRED. |
| SEC. 102.8 CITY AMENDMENTS: EXISTING MECHANICAL |
| EQUIPMENT. AN AGENCY OR LOCAL GOVERNMENT MAY NOT |
| REQUIRE THAT EXISTING MECHANICAL EQUIPMENT LOCATED ON |
| OR ABOVE THE SURFACE OF A ROOF BE INSTALLED IN |
| COMPLIANCE WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE EXCEPT DURING REROOFING WHEN THE |
| EQUIPMENT IS BEING REPLACED OR MOVED AND IS NOT IN |
| COMPLIANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| CODE RELATING TO ROOF-MOUNTED MECHANICAL UNITS. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |