Plan Review Notes For Permit 21020829 |
Permit Number |
21020829 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-03-03 13:23:21 | PROVISO: | | | | FLAT ROOF (BONDED INSULATION OR MEMBRANE) | | GENERAL NOTE #12 OF PRODUCT APPROVAL SUBMITTED REQUIRES | | THAT: "FOR BONDED INSULATION OR MEMBRANE OVER EXISTING | | SUBSTRATES IN A RE-ROOF (TEAR OFF) OR RECOVER | | INSTALLATION, THE EXISTING DECK OR EXISTING ROOF | | SURFACE SHALL BE EXAMINED FOR COMPATIBILITY WITH THE | | ADHESIVE TO BE INSTALLED. IF ANY SURFACE CONDITIONS | | EXIST THAT BRING SYSTEM PERFORMANCE INTO QUESTION, | | FIELD UPLIFT TESTING IN ACCORDANCE SHALL BE CONDUCTED | | ON MOCK-UPS OF THE PROPOSED NEW ROOF ASSEMBLY. FOR | | BONDED INSULATION OR MEMBRANE OVER EXISTING SUBSTRATES | | IN A RECOVER INSTALLATION, THE EXISTING ROOF SYSTEM | | SHALL BE CAPABLE OF RESISTING PROJECT DESIGN PRESSURES | | ON ITS OWN MERIT TO THE SATISFACTION OF THE AUTHORITY | | HAVING JURISDICTION, AS DOCUMENTED THROUGH FIELD UPLIFT | | TESTING. FIELD UPLIFT TESTING SHALL BE IN ACCORDANCE | | WITH ASTM E907, FM LOSS PREVENTION DATA SHEET 1-52 OR | | TESTING APPLICATION STANDARD TS 124." | | |
|