2021-03-05 15:45:35 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 21020721 |
| 3/5/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER: SHOW 2PSI DELIVERY PRESSURE AT THE METER- |
| SECTION G2413.1 FBC RES. |
| |
| 2) GAS RISER: THE CONTRACTOR OR QUALIFIER WHO PREPARED |
| THE DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- |
| SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| & 471.025. |
| |
| 3) THE MARKED UP ENGINEER'S FLOOR PLAN SHOWING THE GAS |
| LINE RUNS IS NOT ACCEPTABLE UNLESS DIGITALLY SIGNED AND |
| SEALED BY THE ENGINEER OF RECORD- - FL. STATUTE 471.025 |
| AND SECTION 61G15-23.005 FAC. |
| |
| 4) IT APPEARS THE NEW GRILL WILL BE INSTALLED UNDER |
| ROOF CONSTRUCTION WHICH MAY REQUIRE A A HOOD SYSTEM PER |
| MANUFACTURER'S SPECIFICATIONS. PLEASE REVIEW THE |
| INSTALLATION GUIDES AND PROVIDE UPDATED DETAILS. |
| |
| 5) THE INCREASE IN VALUE OF $1525.00 APPEARS TO NOT |
| INCLUDE THE COST OF THE GRILL WHICH RETAILS FOR |
| APPROXIMATELY $6300.00. PLEASE ADD THE COST OF THE |
| GRILL TO THE TOTAL INCREASE- SECTION 109.3 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |