2021-03-16 17:00:22 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21030129 |
| 3/16/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHOW THE LOCATION OF THE NEW SHOWER AND BATHTUBS |
| DRAIN ON THE BATHROOM DRAWING, AND PROVIDE A PLUMBING |
| RISER DRAWING- SECTION 107.3.5.3 WPB. PLEASE NOTE IF |
| THE EXISTING TUB AND SHOWER TRAPS ARE REUSED, THE |
| HORIZONTAL DISTANCE FROM THE CENTERLINE OF THE NEW |
| SHOWER AND BATHTUB DRAIN OUTLETS TO THE CENTERLINE OF |
| THE INLET OF THE EXISTING TRAPS SHALL NOT EXCEED 30 |
| INCHES. |
| |
| 2) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & |
| P2709.2 FBC RES. |
| |
| 3) PROVIDE THE DIMENSIONS OF THE SHOWER- SECTION |
| P2708.1 FBC RES. |
| |
| 4) INDICATE THE TYPE OF SHOWER SURROUND FINISH |
| MATERIALS WILL BE INSTALLED AND TO WHAT HEIGHT- SECTION |
| R307.2 FBC RES. |
| |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| WALK-IN TUB, WALK-IN TUB FAUCET AND VALVE- SECTIONS- |
| P2708.4, P2708.5, & P713.2, & P2713.3 FBC RES. THE |
| SPECS SHALL SHOW THE FIXTURES ARE LISTED IN ACCORDANCE |
| WITH THE REQUIRED STANDARDS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |